TRANSFORMERS

TRANSFORMERS FOR HEATING APPLICATIONS

Application
In glass and ceramic melting furnaces
Characteristics Compact, fully-cast design
Standards EXPERT standard

Connection Layout: X, 9, 10, 14
Output Range: 20 - 730 kVA
Secondary Voltages: 3.2 - 98.0 V (multi-stage versions)
 
  • Water cooling
  • Temperature monitoring
  • Measuring coil (for CCR) optional

NOMINAL OUTPUT
S50
(at 50% ED)
SECONDARY CONTINUOUS CURRENT
I2p
SECONDARY VOLTAGE
U20
WEIGHT DIMENSIONS
w x h xd
[ kVA ] [ kA ] [ V ] [ kg ] [ mm ]
30 4.76 3.2 / 4.8 / 6.3 105 ca. 184 x 235 x 528
45 1.18 22 / 26 / 30
34 / 38
160 ca. 184 x 235 x 665
60 9.50 3.2 / 4.8 / 6.3 131 ca. 184 x 235 x 643
80 2.35 22.0 / 26.0
30.0 / 34.0
158 ca. 184 x 235 x 700
110 2.62 34 / 38 / 42 197 ca. 250 x 360 x 615
120 3.16 26.0 / 30.0
24.0 / 38.0
257 ca. 250 x 360 x 600
140 1.42 80.0 / 90.0 / 98.0 270 ca. 250 x 360 x 770
165 2.47 33.3 / 44.4
55.2 / 66.7
430 ca. 280 x 400 x 1,005
380 10.0 19.0 / 25.8
32.0 / 38.0
630 ca. 350 x 500 x 840
730 20.0 18.2 / 25.0
30.8 / 36.4
1,000 ca. 320 x 560 x 1,248